1600kVA transformers
Price: |
1000.0~100000.0 USD |
Payment Terms: |
T/T |
Place of Origin: |
Guangdong, China (Mainland) |
Product Detail
Model No.:
S9-1600kVA
Production Capacity:
100 sets/month
Delivery Date:
15~20days
Coil Structure:
Toroidal
Usage:
Power
Means of Transport:
Ocean
Packing:
wood carton
Phase:
Three
Coil Number:
Autotransformer
Brand Name:
CHAN XING TE
Oil-immersed Distribution Transformer
(Non-Exciting Regulation)
ModelNo. | | S9-1600kVA |
Product Name | | Oil Immersed DistributionTransformer |
| (Non-Exciting Regulation) |
Rated Capacity | kVA | 1600 |
Rated High Voltage | kV | 35 / 38.5 |
High Volt. Tap Range | | ±5% / ±2x2.5% |
Rated Low Voltage | kV | 0.4 |
Phase Number | PH | Three |
Vector Group | | Yyn0 |
No-load Loss | W | 2120 |
Loading Loss | W | 17550 |
No-load Current | % | 0.8 |
Short-circuitimpedance | % | 6.5 |
Oil Weight | kg | 1220.00 |
Machine Weight | kg | 2510.0 |
Weight | kg | 4990 |
BaseGauge (Horizontal*Vertical) | mm | 1070 * 1070 |
OverallDimension | mm | L2660 * W1520 * H2500 |
Oil Immersed Transformers Features: |
1)The oil-immersedtransformer has good insulation performance, flexible and reliable. It can bemade a variety of special-type transformers. |
2)It is advanced designand reasonable structure. Also, it is small size, light weight, easyinstallation, and good economic performance. |
3)It is strong ability over charging, lowloss, low temperature rise, and low noise, |
4)There is reliable shell.It can be run underharsh environment. |
5)Using new type machine structure, there arehigh mechanical strength and strong sudden short-circuit bearing capability. |
6)Good insulation and high level impactinglightning surge, |
7) Fully Sealed Product, no oil conservator,lowers than similar product. It is used vacuum impregnating oil techniques,fully take off the humidity in oil box. It is non-contact with Oil and aircompletely. It is no need to do oil sample test regularly. |
| |
Oil ImmersedTransformers Applications: |
1)outside or inside, |
2)The altitude ofinstallation site can not be over 1000M, the altitude of high pressure modelinstallation site can not be over 4000m, |
3)Environment temperature between +40~-30degrees, |
4)Relative humidity 95%, |
5)The product will be design according tocustomer's requirements when it is used in non-normal condition. |